Serving Atlanta Metro Area & Surrounding Georgia Communities
770-874-0402Your fire alarm system is the backbone of your life safety plan — it detects danger and gives occupants time to evacuate. Titan Life Safety provides thorough NFPA 72-compliant inspections and testing to ensure every component performs when it counts.
NFPA 72 Compliant
All inspections meet current NFPA 72 National Fire Alarm Code requirements
AHJ Reports Provided
Complete inspection documentation for your Authority Having Jurisdiction
Semi-Annual & Annual Service
Flexible scheduling for all required inspection frequencies
Repairs & Troubleshooting
Trouble conditions diagnosed and corrected by our trained technicians
NFPA 72 requires annual inspection and testing of all fire alarm systems by a qualified service technician.
Many systems also require semi-annual testing. Non-compliance can void insurance and result in AHJ violations.
A fire alarm system is only as reliable as its weakest component. We test every device in the system.
Ionization and photoelectric detectors tested for sensitivity and proper response. Spot-type and beam detectors both serviced.
Fixed-temperature and rate-of-rise heat detectors tested per NFPA 72. Used in areas where smoke detectors are not appropriate.
Single and double-action pull stations tested for proper activation and reset. Verified for correct placement per code.
Horns, strobes, and speaker/strobes tested for proper operation, coverage, and candela output per NFPA 72.
Fire alarm control panels inspected for trouble conditions, battery backup, and proper zone identification.
HVAC duct detectors tested for proper airflow response and HVAC shutdown function.
Semi-Annual
Annual
Every 3 Years
Every 10 Years
Dust, insects, and airborne contaminants cause detectors to drift out of sensitivity range, leading to false alarms or missed detection.
Battery backup is required for all fire alarm systems. Weak batteries cause trouble signals and can leave the system unprotected during a power outage.
Devices bypassed to silence nuisance alarms are a serious life safety violation. We identify and correct all bypassed points.
Loss of central station communication means emergency dispatch won't be notified. We verify all monitoring signals are transmitting correctly.
Smoke detectors older than 10 years should be replaced. Obsolete control panels may no longer be serviceable. We identify aging equipment.
Detectors installed too close to HVAC vents, in dead air spaces, or at incorrect heights can fail to detect a fire. We identify placement violations.
We coordinate with your building staff to minimize disruption, notify the monitoring station before testing, and restore the system to full operation before we leave. You receive a complete inspection report the same day.
Pre-Test Coordination
We notify your central station monitoring company and coordinate with building staff before any testing begins.
Device-by-Device Testing
Every initiating device, notification appliance, and control panel function is tested and documented per NFPA 72.
Deficiency Documentation
All deficiencies are documented with device location, type, and the applicable NFPA 72 reference.
System Restore & Report
The system is restored to normal operation, monitoring is re-enabled, and your inspection report is delivered same day.
Stay compliant with NFPA 72 and keep your occupants protected. Call us or request service online.